TM 5-6115-365-15
Section II. OPERATING INSTRUCTIONS
2-3. Setting-Up Instructions
a.
Leveling.
(1)
Locate the trailer on as level a surface as
possible in order for the generator sets to operate
efficiently.
(2)
Set brakes and block wheels securely to
prevent any movement. Operate handbrake at weekly
intervals to assure freedom of linkage.
(3)
Pull the leg support down and adjust
length for firm contact with ground.
Warning
Wheels must be blocked, brakes set,
and leg support down in support
position before attempting to roll up
the tarpaulin and before starting to
assemble or set-up the equipment for
operation.
b.
Grounding.
Warning
Never operate the generator set until
it
has
been
properly
grounded.
Electrical defects in the load lines or
equipment
can
cause
death
by
electrocution when contact is made
with an ungrounded system.
(1)
The generator set must be grounded prior
to operation. The ground may be any of three methods,
depending on the location and terrain.
(a)
The ground rod driven to a depth of
8 feet.
(b)
An
underground
metallic
water
piping system.
(c)
A metal plate (9 sq ft) buried at a
depth of 4 feet.
(2)
The ground lead must be No. 6 AWG
copper wire bolted or clamped to the rod, plate, or piping
system.
(3)
Connect the other end of the ground lead
to the generator set ground stud as shown in figure 2-2.
(4)
Be
sure
that
both
generators
are
connected to the generator set ground stud as shown in
figure 2-2.
c.
Preparation for Starting.
(1)
Remove the canvas tarpaulin and remove
the racks.
(2)
Open the trailer tailgate and remove all
loose auxiliary items and anything else that might block
the free circulation of air through the trailer and around
the generator sets.
Caution
It is of foremost importance that
there be free circulation of air around
the generator sets at all times during
operation. Inadequate ventilation is a
major cause of damage to the
equipment.
(3)
Be sure the transfer switch load cables
are connected to the generator sets as illustrated in
figure 2-3.
(4)
Connect the fuel hoses as illustrated in
figure 2-4.
Warning
Never operate the generator set in an
enclosed area unless the exhaust
gases are piped to the outside.
Inhalation of exhaust fumes will
result in serious illness or death.
2-4. Starting
a.
Perform setting-up and pre-starting procedures
(para 2-3).
b.
Be sure generator transfer switch is OFF
(fig. 2-3).
c.
Start
the
generator
set
as
instructed
in
TM 5-6115-271-14.
2-5. Stopping
a.
Turn generator transfer switch OFF or in position
to select standby generator (fig. 2-3).
b.
Stop
the
generator
set
as
instructed
in
TM 5-6115-271-14.
2-6. Operation
a.
Start the generator (para 2-4) and position
transfer switch to desired generator.
b.
Operate
the
generator
as
instructed
in
TM 5-6115-271-14.
c.
Perform the fuel transfer procedure as instructed
in figure 2-4.
Change 8 2-3