TM 9-6115-730-24
0063
WARNING
DC voltages are present at generator set electrical components even with generator set shut
down. Avoid shorting any positive with ground/negative. Failure to comply can cause injury to
personnel and damage to equipment.
Diesel fuel is flammable and toxic to eyes, skin, and respiratory tract. Skin and eye protection are
required when working in contact with diesel fuel. Avoid repeated or prolonged contact. Provide
adequate ventilation. Failure to comply can cause injury or death to personnel.
CAUTION
All fittings and openings must be capped or plugged immediately after opening to prevent
REMOVAL
1. Ensure generator set is fully stopped, ENGINE CONTROL switch is OFF/RESET, Battery Disconnect Switch is
OFF, and DEAD CRANK SWITCH is OFF before proceeding.
2. Remove four screws (Figure 1, item 1), four nuts (Figure 1, item 2), washers (Figure 1, item 3) two hold down
assemblies (Figure 1, item 4), and fuel tank (Figure 1, item 5).
END OF TASK
REPAIR
Repair damage to fuel tank with adhesive repair kit, following directions provided with the kit.
END OF TASK
INSTALLATION
1. Install fuel tank (Figure 1, item 5), two hold down assemblies (Figure 1, item 4), four screws (Figure 1, item 1),
washers (Figure 1, item 3), and nuts (Figure 1, item 2).