TM 9-6115-730-10
0012 00
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING LUBRICATION
INSTRUCTIONS Continued
Table 1. Preventive Maintenance Checks and Services Continued.
LOCATION/
NOT FULLY
ITEM
ITEM TO
MISSION
NO.
INTERVAL
CHECK/SERVICE
PROCEDURE
CAPABLE IF:
20
Before
Output Load
Check for loose or damaged wiring or load
Loose or damaged
Terminal Board
cables inside generator set.
wiring or cables.
Check output terminals for damaged or
Damaged, loose or
missing hardware.
missing hardware.
21
Before
Reconnection Board
Verify position of Reconnection Board and
Reconnection Board
check to see if it is in the correct position
is set for incorrect
for voltage outputs required by load.
voltage output.
Notify maintenance if repositioning is
required.
CONTROL PANEL
ASSEMBLY
__________
WARNING
and become entangled in generator set
components. Remove all metal jewelry
to comply can cause injury or death to
personnel.
DC voltages are present at generator set
electrical components even with
generator set shut down. Avoid
shorting any positive with
ground/negative. Failure to comply can
cause injury to personnel and damage to
equipment.
Set DEAD CRANK SWITCH to NORMAL
Set Battery Disconnect Switch to ON
Set ENGINE CONTROL switch to COOL
22
Before
Indicators and
Check all indicators and controls for
Indicators or controls
Controls
damaged or missing parts.
damaged or
missing.
Before
Control Panel Wiring
Loose or damaged
23
Check for loose or damaged wiring or
Harness
wiring or
connectors.
connectors.
0012 00-8