TM 9-6115-729-10
100 kW TACTICAL QUIET GENERATOR SET
0005 00
DESCRIPTION AND USE OF OPERATOR CONTROLS AND INDICATORS Continued
GENERATOR SET CONTROL Continued
Table 2. Generator Set Control Controls and Indicators Continued.
CONTROL OR
KEY
INDICATOR
FUNCTION
13-19
Keypad
Used to control information shown on upper display and lower display.
13
POWER METER
Displays power data to lower display. When pressed, following functions scroll
automatically:
Total real power (kW)
Total reactive power (KVAR)
Percentage of rated power (%kW)
Power factor (average) (PF)
Display scrolling stops when operator presses key for less than 5 seconds. Display
will show a particular parameter continuously.
Additional functions will scroll if key held for more than 5 seconds:
Total real power (kW)
Real power phase A (kW)
Real power phase B (kW)
Real power phase C (kW)
Total apparent power (kVA)
Total reactive power (KVA)
Percentage of rated power (%kW)
Power factor (average) (PF)
Power factor phase A
Power factor phase B
Power factor phase C
Total energy output (kWh)
Total reactive energy output (kVARHr)
14
AC METER
Selects phase of generator output that is shown on upper display. Pressing this key
allows operator to check voltage, current, and frequency of each phase one at a
time. Options are as follows:
Voltage (average), frequency, current (total)
Voltage (line to line), frequency, current (line) for any one phase
Voltage (line to line) for all three phases at once
Current (line) for all three phases at once
Voltage (line to neutral) for all three phases at once
0005 00-8