TM 9-6115-669-13&P
Table 2-1 Control Cabinet Assembly, Description of Controls and Indicators (continued).
Item
Number
28
AC CIRCUIT INTERRUPTER ON
illuminated pushbutton switch, green
(S8, H14)
29
VOLTAGE ADJUST potentiometer,
10 turn (R3)
Set between 4 and 5
30
31
AC CIRCUIT INTERRUPTER OFF
pushbutton switch (S7)
VOLTAGE SELECTOR SWITCH
(S11)
L3-L1, L2-L3, L1-L2
L1-N, L2-N, L3-N
32
PARALLEL OPERATION ON illumi-
nated pushbutton switch, white (S9,
H12)
33
PANEL DIMMER with switch (S16,
Adjusts panel light brightness and shuts off
R2)
lights
34
35
36
S16 off, R2 turned all the way left
S16 on, R2 turned to the right
FUEL TANK PUMP ON illuminated
pushbutton switch, green (S19, H16)
LAMP TEST pushbutton switch (S20)
FUEL TANK PUMP OFF pushbutton
switch (S18)
37
GLOWPLUG ON lamp, amber (H1)
Description
Function
Turns on power system (main contactor),
H14 lights up when power is ON
Adjusts generator voltage:
For rated voltage indicated on VOLTAGE
meter (11)
Shuts down power system (main contactor);
H14 goes out when power is OFF
Line voltages
Phase voltages
Indicated on VOLTAGE meter (11)
Initiates synchronization;
H12 lights up during synchronization
All active lights at minimum brightness
All lights at maximum brightness
Turns fuel pump on;
H16 lights up when fuel pump is on
Tests operation of front panel lamps
Shuts fuel pump off,
H16 goes out when fuel pump is off
Lights up about 90 seconds after glowplug
operation begins
2 - 5