TM 9-6115-669-13&P
N O T E
The synchronous generator is activated in approximately 90
seonds.
N O T E
If the diesel engine or the synchronous generator malfunc-
tions during operation, the main contractor K1 or Generator
Set 160 kW will shut down.
c.
Read OIL PRESSURE meter (11): 3 - 5 bare.
d.
Read BATTERY CHARGE meter (20): 10 - 60 A.
e.
Read FREQUENCY meter (8): 400.0 ±0.2 Hz.
If reading is different, set frequency with the FREQUENCY ADJUST potentiometer (13) and
lock in place with locking lever (12).
f.
Set VOLTAGE SELECTOR SWITCH (17) to L1-L2, then L2-L3, then L3-L1, and read VOLT-
AGE meter (6): 208 ±2 V.
If reading is different, set voltage with the VOLTAGE ADJUST potentiometer (16) and lock in
place with locking lever (15).
g.
Set VOLTAGE SELECTOR SWITCH (17) to L1-N, then L2-N, then L3-N, and check VOLT-
AGE meter (6): 120 ±1 V.
2 - 52
Change 1