TM 5-6115-631-14&P
Figure 4-13. Power Cable Replacement.
to TM 5-6115-584-12.)
(g) Connect power cable to load terminals on generator set. (Refer
e. Ground Wire Replacement (5-Wire Switch Box). (See figure 4-14.) In the 5-wire switch box
only, a wire connects load terminal LO to AC GROUND terminal E2 located on the side of the switch box
below the terminal board.
(1) Removal
(a)
(b)
(c)
(d)
Remove 16 screws (1, figure 4-14), 16 Iockwashers (2) and 16 flat washers (3) secur-
ing cover (4) to switch box (5) and take cover off switch box.
Remove nut (6) and Iockwasher (7) from load terminal L0 (8) inside switch box.
Slide power cable ground (white) wire terminals (9) and switch box ground wire terminal
(10) off load terminal L0 (8).
Remove nut (11) and Iockwasher (12) from AC GROUND terminal E2 (13) inside box.
Remove ground wire terminal (14).
4-26